DL型系列冷風(fēng)機(jī)主要技術(shù)參 數(shù): 散熱片間距:4.5mm
型號(hào) | 制冷量 | 蒸發(fā)面積 | 風(fēng)機(jī) | 電加熱融霜 | 重量 | ||||||
直徑 | 風(fēng)量 | 電壓 | 功率 | 射程 | 盤管 | 水盤 | 電壓 | ||||
DL-2.1/10 | 2.1 | 10 | 330 | 1700 | 380 | 90 | 9 | 0.7 | 0.7 | 220 | 20 |
DL-3.1/15 | 3.1 | 15 | 330 | 2*1700 | 380 | 2*90 | 9 | 1.0 | 1.0 | 220 | 28 |
DL-4.2/20 | 4.2 | 20 | 330 | 2*1700 | 380 | 2*90 | 9 | 1.0 | 1.0 | 220 | 35 |
DL-5.2/25 | 5.2 | 25 | 330 | 3*1700 | 380 | 3*90 | 9 | 1.2 | 1.2 | 220 | 42 |
DL-8.20/40 | 8.2 | 40 | 400 | 2*3000 | 380 | 2*250 | 12 | 1.4 | 0.7 | 220 | 65 |
DL-11.5/55 | 11.5 | 55 | 400 | 2*3000 | 380 | 2*250 | 12 | 1.4 | 0.7 | 220 | 72 |
DL-16.7/80 | 16.7 | 80 | 500 | 2*6000 | 380 | 2*550 | 15 | 3.0 | 1.5 | 220 | 97 |
DL-22.0/105 | 22.0 | 105 | 500 | 2*6000 | 380 | 2*550 | 15 | 3.0 | 1.5 | 220 | 116 |
DL-25.8/125 | 25.8 | 125 | 500 | 3*6000 | 380 | 3*550 | 15 | 3.8 | 1.9 | 220 | 140 |
DL-33.6/160 | 33.6 | 160 | 500 | 3*6000 | 380 | 3*550 | 15 | 4.6 | 2.3 | 220 | 160 |
DL-38.7/185 | 38.7 | 185 | 500 | 4*6000 | 380 | 4*550 | 15 | 5.4 | 2.7 | 220 | 195 |
DL-44.0/210 | 44.0 | 210 | 500 | 4*6000 | 380 | 4*550 | 15 | 6.0 | 3.0 | 220 | 208 |
DL-52.9/260 | 52.9 | 260 | 600 | 2*10000 | 380 | 2*1500 | 17 | 9.0 | 1.8 | 220 | 296 |
DL-67.2/330 | 67.2 | 330 | 600 | 3*10000 | 380 | 2*1500 | 17 | 11.0 | 2.2 | 220 | 376 |
DL-83.4/410 | 83.4 | 410 | 600 | 3*10000 | 380 | 3*1500 | 17 | 13.0 | 2.6 | 220 | 435 |
備注:1.數(shù)據(jù)如有變動(dòng)恕不另行通知。 2.根據(jù)用戶冷風(fēng)機(jī)需要可另行加工
DL型冷風(fēng)機(jī)安裝尺寸:
型號(hào) | A | B | H | D | E | E1 | E2 | E3 | F | 接口管徑 | 排水管直徑 | 外觀示意圖
| |
進(jìn)口 | 出口 | ||||||||||||
DL-2.1/10 | 730 | 425 | 440 | 260 | 530 | / | / | / | 85 | 12 | 16 | 1 | ![]() |
DL-3.1/15 | 1130 | 425 | 440 | 260 | 930 | / | / | / | 85 | ![]() | |||
DL-4.2/20 | 1280 | 425 | 440 | 260 | 1080 | / | / | / | 85 | ||||
DL-5.2/25 | 1580 | 425 | 440 | 260 | 1380 | / | / | / | 85 | ![]() | |||
DL-8.2/40 | 1520 | 600 | 560 | 370 | 1250 | 600 | / | / | 95 | 16 | 25 | ![]() | |
DL-11.5/55 | 1520 | 600 | 560 | 370 | 1250 | 600 | / | / | 95 | ||||
DL-16.7/80 | 1820 | 650 | 660 | 420 | 1550 | 950 | / | / | 95 | 19 | 38 | ||
DL-21.9/105
| 1820 | 650 | 660 | 420 | 1550 | 750 | / | / | 95 | ||||
DL-25.8/125 | 2300 | 650 | 660 | 420 | 2030 | 660 | 660 | / | 95 | ![]() | |||
DL-33.6/160 | 2720 | 650 | 660 | 420 | 2450 | 800 | 800 | / | 95 | ||||
DL-38.7/185 | 3120 | 650 | 660 | 420 | 2850 | 700 | 700 | 700 | 95 | 25 | 50 | 1.5 | ![]() |
DL-44.0/210 | 3520 | 650 | 660 | 420 | 3250 | 800 | 800 | 800 | 95 | ||||
DL-52.9/260 | 2220 | 1060 | 860 | 630 | 1950 | 950 | / | / | 95 | 25 | 50 | ![]() | |
DL-67.2/330 | 2720 | 1060 | 860 | 630 | 2450 | 800 | 800 | / | 95 | ![]() | |||
DL-83.4/410 | 3200 | 1060 | 860 | 630 | 2930 | 960 | 960 | / | 95 |
1、 安裝時(shí),應(yīng)保證氣流通暢,冷庫內(nèi)送風(fēng)均勻,維修方便。冷風(fēng)機(jī)的風(fēng)扇射程為7米,安裝時(shí)應(yīng)注意長度大于7米的冷庫庫溫均勻。
2、 風(fēng)機(jī)的排風(fēng)方向應(yīng)盡可能朝向門,吸風(fēng)側(cè)應(yīng)避開門。離墻距離應(yīng)符合下圖之規(guī)定:
3、 供液管的配置應(yīng)保證供液量的充足,膨脹閥前無閃發(fā)氣體;回氣管的配置應(yīng)保證回油流暢,壓損不超過2PSIG?;貧夤艹稣舭l(fā)器后,上升時(shí)應(yīng)加一回油彎,上升段要縮徑。
4、特大型冷庫其頂板需要用立柱支撐。在底板上鋸出柱子穿孔,將立柱用膨脹螺栓固定于地面。將鋼梁掉起,焊接于立柱上。如高度需調(diào)整時(shí),在鋼梁與立柱之間加墊鐵。頂板放于鋼梁上。并做好庫板之間的密封,安裝裝飾件。
當(dāng)兩個(gè)以上的冷庫并聯(lián)為一路系統(tǒng)時(shí),每個(gè)冷庫應(yīng)配一電磁閥,以保證每個(gè)冷庫供液均勻。
膨脹閥感溫包應(yīng)安裝在盡可能靠近蒸發(fā)器的回氣管的水平位置上,并注意以下事項(xiàng):
l 感溫包決不能安裝在吸氣管底部
l 感溫包必須能感受過熱的蒸汽溫度,不得暴露在極冷或極熱的位置,否則建議將感溫包隔熱。
l 感溫包應(yīng)安裝在回氣管截面的1點(diǎn)和4點(diǎn)的水平線上。不能安裝在吸氣管的底部,以防吸氣管底部有油,使感溫包接受錯(cuò)誤信號(hào)。
2、安裝:風(fēng)機(jī)橫吊桿直線貼頂板安裝。
1)M10×200鍍鋅螺栓
2)Æ10彈簧墊圈
3)空氣冷卻器橫吊桿
4)風(fēng)機(jī)安裝板
5)Æ10木墊圈
6)M10螺母
3、排水管:
低溫冷庫應(yīng)安裝下水防凍加熱絲后,再連接PVC管。庫內(nèi)排水管盡可能短,采用Æ25或Æ40的PVC管。水盤泄水口向庫外方向是5%斜坡的外排水。排水管庫外段需作一水封。